SRO 24M

Electromechanical relay, normally open.

 

 

Datasheet
Qualifications checkbox_on CE checkbox_on RoHS checkbox_on cULus
Delcon
MTTF (Mean Time To Failure): Depends on load and switching frequency.
PrimarySRO 24M
Input voltagenominalVDC24
Input currenttypicalmA9
maximummA-
Input voltage rangeminimumVDC19
maximumVDC32
Input impedancetypicalkΩ2,7
Switch-on voltagetypicalVDC-
maximumVDC19
Switch-off voltagetypicalVDC-
minimumVDC2,5
SecondarySRO 24M
Load voltageminimumVAC/VDC0
nominalVAC/VDC240/250
maximumVAC/VDC265/300
Load currentmaximumA6
Switch-on delaytypicalms5
maximumms10
Switch-off delaytypicalms10
maximumms15
Load inductance at 60 V 3 A, L/Rmaximumms0,5
Load inductance at 24 V 2 A, L/Rmaximumms5
Mechanical lifeminimumoperations10 000 000
ContactsmaterialAgSNO2
Main specificationsSRO 24M
Operating temperaturerange°C-25...+70