SLO 24IRA

AC-output relay for resistive and inductive loads, fast switch-off. 

Datasheet
Qualifications checkbox_on CE checkbox_on RoHS checkbox_on cULus
Delcon
MTTF (Mean Time To Failure): 34,2 years
PrimarySLO 24IRA
Input voltagenominalVDC24
Input currenttypicalmA12
maximummA15
Input voltage rangeminimumVDC18
maximumVDC32
Input impedancetypicalkΩ2
Switch-on voltagetypicalVDC16
maximumVDC18
Switch-off voltagetypicalVDC14
minimumVDC12
SecondarySLO 24IRA
Load voltageminimumVAC/VDC0
nominalVAC/VDC240/250
maximumVAC/VDC265/300
Load currentmaximumA1,2
Voltage drop at maximum loadtypicalVAC1,5
Switch-on delaytypicalms0,3
maximumms0,5
Switch-off delaytypicalms0,3
maximumms0,5
Load inductance at 240 VAC 1,2 Arangecos Φ0,3...1
Leakage current (off-state)typicalmA (AC)0,05