DC-output relay for inductive loads and to cut off high DC voltages.
| Primary | SLO 24CRA4 | ||
| Input voltage | nominal | VDC | 24 |
| Input current | typical | mA | 12 |
| maximum | mA | 15 | |
| Input voltage range | minimum | VDC | 18 |
| maximum | VDC | 32 | |
| Input impedance | typical | kΩ | 2 |
| Switch-on voltage | typical | VDC | 16 |
| maximum | VDC | 18 | |
| Switch-off voltage | typical | VDC | 14 |
| minimum | VDC | 12 | |
| Secondary | SLO 24CRA4 | ||
| Load voltage | minimum | VDC | 0 |
| nominal | VDC | 250 | |
| maximum | VDC | 300 | |
| Load current | maximum | A | 4 |
| Voltage drop at maximum load | typical | VDC | 0,6 |
| Switch-on delay | typical | ms | 0,3 |
| maximum | ms | 0,5 | |
| Switch-off delay | typical | ms | 0,3 |
| maximum | ms | 0,5 | |
| Load inductance at 250 V 4 A, L/R | maximum | ms | 5 |
| Load inductance at 24 V 4 A, L/R | maximum | ms | 50 |
| Leakage current (off-state) | maximum | mA | 1 |