SLO 220CRA

DC-output relay for inductive loads and to cut off high DC voltages. 

 

Datasheet
Qualifications checkbox_on CE checkbox_on cULus
Delcon
MTTF (Mean Time To Failure): 26,3 years
PrimarySLO 220CRA
Input voltagenominalVDC220
Input currenttypicalmA3,5
maximummA4,0
Input voltage rangeminimumVDC190
maximumVDC250
Input impedancetypicalkΩ63
Switch-on voltagetypicalVDC170
maximumVDC190
Switch-off voltagetypicalVDC120
minimumVDC80
SecondarySLO 220CRA
Load voltageminimumVDC0
nominalVDC250
maximumVDC300
Load currentmaximumA1,8
Voltage drop at maximum loadtypicalVDC1
Switch-on delaytypicalms0,5
maximumms1
Switch-off delaytypicalms0,5
maximumms1
Load inductance at 250 V 1,8 A, L/Rmaximumms10
Load inductance at 24 V 1,8 A, L/Rmaximumms100
Leakage current (off-state)maximummA1