SLO 12CRA

DC-output relay for inductive loads and to cut off high DC voltages.

Datasheet
Qualifications checkbox_on CE checkbox_on cULus
Delcon
MTTF (Mean Time To Failure): 70,8 years
PrimarySLO 12CRA
Input voltagenominalVDC12
Input currenttypicalmA9
maximummA12
Input voltage rangeminimumVDC9
maximumVDC18
Input impedancetypical1,3
Switch-on voltagetypicalVDC8
maximumVDC9
Switch-off voltagetypicalVDC7
minimumVDC6
SecondarySLO 12CRA
Load voltageminimumVDC0
nominalVDC250
maximumVDC300
Load currentmaximumA1,8
Voltage drop at maximum loadtypicalVDC1
Switch-on delaytypicalms0,3
maximumms0,5
Switch-off delaytypicalms0,3
maximumms0,5
Load inductance at 250 V 1,8 A, L/Rmaximumms10
Load inductance at 24 V 1,8 A, L/Rmaximumms100
Leakage current (off-state)maximummA1