SLI 48CRI

DC-input relay for limit switches. Normally closed operation.

 

 

 

Datasheet
Qualifications checkbox_on CE checkbox_on RoHS
Delcon
MTTF (Mean Time To Failure): 525,1 years
PrimarySLI 48CRI
Input voltagenominalVDC48
Input currenttypicalmA6
maximummA8
Input voltage rangeminimumVDC40
maximumVDC70
Input impedancetypicalkΩ8
Switch-on voltagetypicalVDC36
maximumVDC40
Switch-off voltagetypicalVDC26
minimumVDC20
SecondarySLI 48CRI
Load voltageminimumVDC0
maximumVDC60
Load currentmaximummA100
Voltage drop at 30 mA loadtypicalVDC0,3
maximumVDC0,5
Switch-on delaytypicalms0,5
Switch-off delaytypicalms0,5
Leakage current (on-state)maximumµA10