SLI 230CR

AC-input relay for limit switches and long cables.

 

 

 

 

 

Datasheet
Qualifications checkbox_on CE checkbox_on RoHS checkbox_on cULus
Delcon
MTTF (Mean Time To Failure): 17 years
PrimarySLI 230CR
Input voltagenominalVAC220...240
Input current at nominal voltagetypicalmA4,6
maximummA5
Input voltage rangeminimumVAC190
maximumVAC265
Input impedancetypicalkΩ50
Switch-on voltagetypicalVAC170
maximumVAC190
Switch-off voltagetypicalVAC110
minimumVAC80
SecondarySLI 230CR
Load voltageminimumVDC0
maximumVDC60
Load currentmaximummA50
Voltage drop at maximum loadtypicalVDC0,2
maximumVDC0,4
Switch-on delaytypicalms50
Switch-off delaytypicalms50
Leakage current (off-state)maximumµA1