DC-input relay for limit switches.
| Primary | SLI 125CR | ||
| Input voltage | nominal | VDC | 110...125 |
| Input current at nominal voltage | typical | mA | 4 |
| maximum | mA | 4,1 | |
| Input voltage range | minimum | VDC | 95 |
| maximum | VDC | 140 | |
| Input impedance | typical | kΩ | 31 |
| Switch-on voltage | typical | VDC | 80 |
| maximum | VDC | 95 | |
| Switch-off voltage | typical | VDC | 60 |
| minimum | VDC | 50 | |
| Secondary | SLI 125CR | ||
| Load voltage | minimum | VDC | 0 |
| maximum | VDC | 60 | |
| Load current | maximum | mA | 50 |
| Voltage drop at max. load | typical | VDC | 0,2 |
| maximum | VDC | 0,4 | |
| Switch-on delay | typical | ms | 0,3 |
| Switch-off delay | typical | ms | 0,3 |
| Leakage current (off-state) | maximum | µA | 1 |