SLI 120CR

AC-input relay for limit switches and long cables.

 

 

 

 

 

Datasheet
Qualifications checkbox_on CE checkbox_on RoHS checkbox_on cULus
Delcon
MTTF (Mean Time To Failure): 36,5 years
PrimarySLI 120CR
Input voltagenominalVAC110...120
Input current at nominal voltagetypicalmA5,6
maximummA6
Input voltage rangeminimumVAC95
maximumVAC140
Input impedancetypicalkΩ21
Switch-on voltagetypicalVAC80
maximumVAC95
Switch-off voltagetypicalVAC60
minimumVAC50
SecondarySLI 120CR
Load voltageminimumVDC0
maximumVDC60
Load currentmaximummA50
Voltage drop at maximum loadtypicalVDC0,2
maximumVDC0,4
Switch-on delaytypicalms40
Switch-off delaytypicalms50
Leakage current (off-state)maximumµA1