Solid state DC output relays for resistive loads up to 10 A.
In the same narrow package size than standard relay, these relays are rated at 10 A continuous and 80 A surge currents.
With inductive loads a clamp diode (not Zener) must be installed in the poles of the load.
For highly inductive loads we recommend to use SLO ...CRA or SLO ...CRA4.
Download specifications for DIN-rail socket MOS 1N for output plug-in relays in pdf format.
Specification for the old version can be downloaded here.
Electrical specifications for the DIN-rail relays are same than for the plug-in relays.
Mechanical details in pdf format for DIN-rail output relays can be downloaded here.
Details for old version are here.
Color of casing: red
Specifications at 25 °C. See derating
| PRIMARY |
|
|
SLO 5CRX |
SLO 12CRX |
SLO 24CRX |
| Input voltage |
nominal |
VDC |
5 |
12 |
24 |
| Input current at nominal voltage |
typical |
mA |
12 |
9 |
12 |
| maximum |
mA |
15 |
12 |
15 |
| Input voltage range (abs.) |
minimum |
VDC |
3,0 |
9 |
18 |
| maximum |
VDC |
7,0 |
18 |
32 |
| Input impedance |
typical |
kΩ |
0,42 |
1,3 |
2,0 |
| Switch-on voltage |
typical |
VDC |
2,7 |
8 |
16 |
| maximum |
VDC |
3,0 |
9 |
18 |
| Switch-off voltage |
typical |
VDC |
2,5 |
7 |
14 |
| minimum |
VDC |
2,0 |
6 |
12 |
| SECONDARY |
|
|
|
|
|
Load voltage
(absolute) |
minimum |
VDC |
0 |
0 |
0 |
| nominal |
VDC |
24 |
24 |
24 |
| maximum |
VDC |
32 |
32 |
32 |
| Load current cont. |
maximum |
A |
10 |
10 |
10 |
| Load current 10 ms |
maximum |
A |
80 |
80 |
80 |
| Drop at max. load |
typical |
V |
0,4 |
0,4 |
0,4 |
| Switch-on delay |
typical |
ms |
0,3 |
0,3 |
0,3 |
| maximum |
ms |
0,5 |
0,5 |
0,5 |
| Switch-off delay |
typical |
ms |
0,3 |
0,3 |
0,3 |
| maximum |
ms |
0,5 |
0,5 |
0,5 |
| Inductive load L/R |
maximum |
ms
|
0,5 (32 V/10 A) |
0,5 (32 V/10 A) |
0,5 (32 V/10 A) |
| ms |
2 (24 V/5 A) |
2 (24 V/5 A) |
2 (24 V/5 A) |
| Operating temperature |
|
°C |
-25...+70 |
-25...+70 |
-25...+70 |