| AC INPUT |
POSSIBLE REASONS |
TECHNICAL ASPECTS |
DELCON SOLUTION |
| Relays/optos operate by them selves. |
Capacitive leakage due to long signal wires and/or parallel lying signal and load cables. |
100 m wire´s capacitance can be up to 10 nF. This generates relatively high voltage in the cable. |
SLI ...CR |
| Relays/optos do not release. |
| Reason to failure is difficult to find due to unreliable status indication. |
LED is glowing even the relay/opto is not on. |
Operation and signal is not in synchrone. Capacitive leakage. |
| Indefinite operation of proxy |
2 wire proxy with snubber in secondary |
High leakage current + capacitive leakage |
SLI ...CRP |
| Optos break suddenly. |
High transients from field |
Poor protection in primary |
SLI ...CH |